IEC koblingsklasser | |||
---|---|---|---|
Current | Category | Typical Applications | Relevant IEC Product Standard (3) |
A.C. | AC-1 | Non Inductive or slightly inductive loads, resistance furnaces, heaters | 60947-4 |
AC-2 | Slip-ring motors: switching off | ||
AC-3 | Squirrel-cage motors: starting, switching off motors during running Most typical industrial application | ||
AC-4 | Squirrel-cage motors: starting, plugging(1), inching (2) | ||
AC-5a | Switching of electric discharge lamps | ||
AC-5b | Switching of incandescent lamps | ||
AC-6a | Switching of transformers | ||
AC-6b | Switching of capacitor banks | ||
AC-7a | Slightly inductive loads in household appliances: mixers, blenders | ||
AC-7b | Motor-loads for household applications: fans, central vacuum | ||
AC-8a | Hermetic refrigerant compressor motor control with manual resetting overloads | ||
AC-8b | Hermetic refrigerant compressor motor control with automatic resetting overloads | ||
AC-12 | Control of resistive loads and solid state loads with opto-coupler isolation | 60947-5 | |
AC-13 | Control of solid state loads with transformer isolation | ||
AC-14 | Control of small electromagnetic loads | ||
AC-15 | Control of A.C. electromagnetic loads | 60947-3 | |
AC-20 | Connecting and disconnecting under no-load conditions | ||
AC-21 | Switching of resistive loads, including moderate loads | ||
AC-22 | Switching of mixed resistive and inductive loads, including moderate overloads | ||
AC-23 | Switching of motor loads or other highly inductive loads | ||
A.C. and D.C | A | Protection of circuits, with no rated short-time withstand current | 60947-2 |
B | Protection of circuits, with a rated short-time withstand current | ||
D.C | DC-1 | Non Inductive or slightly inductive loads, resistance furnaces, heaters | 60947-4 |
DC-3 | Shunt-motors, starting, plugging(1), inching(2), dynamic breaking of motors | ||
DC-5 | Series-motors, starting, plugging(1), inching(2), dynamic breaking of motors | ||
DC-6 | Switching of incandescent lamps | ||
DC-12 | Control of resistive loads and solid state loads with opto-coupler isolation | ||
DC-13 | Control of D.C. electromagnetics | 60947-5 | |
DC-14 | Control of D.C. electromagnetic loads having economy resistors in the circuit | ||
DC-20 | Connecting and disconnecting under no-load conditions | ||
DC-21 | Switching of resistive loads, including moderate overloads | 60947-3 | |
DC-22 | Switching of mixed resistive and inductive loads, including moderate overloads (i.e.shunt motors) | ||
DC-23 | Switching of highly inductive loads (I.e. series motors) | ||
(1) Plugging - Stopping a motor rapidly by reversing the primary power connections. (2) Inching - Energizing a motor repeatedly for short periods to obtain small incremental movements. (3) IEC Standards must be purchased from the International Electrotechnical Commission |