CurrentCategoryTypical ApplicationsRelevant IEC
Product Standard (3)
A.C. AC-1Non Inductive or slightly inductive loads, resistance furnaces, heaters 60947-4
AC-2Slip-ring motors: switching off
AC-3Squirrel-cage motors: starting, switching off motors during running Most typical industrial application
AC-4Squirrel-cage motors: starting, plugging(1), inching (2)
AC-5aSwitching of electric discharge lamps
AC-5bSwitching of incandescent lamps
AC-6aSwitching of transformers
AC-6bSwitching of capacitor banks
AC-7aSlightly inductive loads in household appliances: mixers, blenders
AC-7bMotor-loads for household applications: fans, central vacuum
AC-8aHermetic refrigerant compressor motor control with manual resetting overloads
AC-8bHermetic refrigerant compressor motor control with automatic resetting overloads
AC-12Control of resistive loads and solid state loads with opto-coupler isolation 60947-5
AC-13Control of solid state loads with transformer isolation
AC-14Control of small electromagnetic loads
AC-15Control of A.C. electromagnetic loads 60947-3
AC-20Connecting and disconnecting under no-load conditions
AC-21Switching of resistive loads, including moderate loads
AC-22Switching of mixed resistive and inductive loads, including moderate overloads
AC-23Switching of motor loads or other highly inductive loads
A.C. and D.C AProtection of circuits, with no rated short-time withstand current 60947-2
BProtection of circuits, with a rated short-time withstand current
D.C DC-1Non Inductive or slightly inductive loads, resistance furnaces, heaters 60947-4
DC-3Shunt-motors, starting, plugging(1), inching(2), dynamic breaking of motors
DC-5Series-motors, starting, plugging(1), inching(2), dynamic breaking of motors
DC-6Switching of incandescent lamps
DC-12Control of resistive loads and solid state loads with opto-coupler isolation
DC-13Control of D.C. electromagnetics 60947-5
DC-14Control of D.C. electromagnetic loads having economy resistors in the circuit
DC-20Connecting and disconnecting under no-load conditions
DC-21Switching of resistive loads, including moderate overloads 60947-3
DC-22Switching of mixed resistive and inductive loads, including moderate overloads (i.e.shunt motors)
DC-23Switching of highly inductive loads (I.e. series motors)
  (1) Plugging - Stopping a motor rapidly by reversing the primary power connections.
(2) Inching - Energizing a motor repeatedly for short periods to obtain small incremental movements.