IT-standarder
Betegnelser for skærmning
F/UTP: Folieskærm under kappen, lederpar uskærmet.
S/FTP: Skærmet under kappen, lederpar folieskærmet.
SF/UTP: Skærmet og folieskærmet under kappen, lederpar uskærmet.
U/FTP: Uskærmet under kappen, lederpar folieskærmet.
UTP: Uskærmet under kappen, lederpar uskærmet (også kendt som U/UTP).
Argumenter for anvendelse af skærmede kabler
- Lettere bygningsdesign fordi afstandskrav er enklere
- Energibesparelse. Kat.6A har negativ ACR og bruger derfor meget energi på at forbedre signal/støj-forholdet.
- Pga. negativ ACR *, skal switche resettes hver gang støjen bliver for kraftig.
* ACR=Attenuation Crosstalk Ratio, also known as headroom, is a calculation of the difference between attenuation and crosstalk in a networking transmission.
Nyttige standarder
ISO 11801 General-purpose telecommunication cabling systems (structured cabling)
Beskriver de forskellige kabelkategorier (kilde Wikipedia)
Class A: up to 100 kHz using category 1 cables and connectors
Class B: up to 1 MHz using category 2 cables and connectors
Class C: up to 16 MHz using category 3 cables and connectors
Class D: up to 100 MHz using category 5e cables and connectors
Class E: up to 250 MHz using category 6 cables and connectors
Class EA: up to 500 MHz using category 6A cables and connectors (Amendment 1 and 2 to ISO/IEC 11801, 2nd Ed.)
Class F: up to 600 MHz using category 7 cables and connectors
Class FA: up to 1 GHz using category 7A cables and connectors(Amendment 1 and 2 to ISO/IEC 11801, 2nd Ed.)
Class I: up to 2 GHz using category 8.1 cables and connectors (ISO/IEC 11801-1, Edition 1.0 2017-11)
Class II: up to 2 GHz using category 8.2 cables and connectors (ISO/IEC 11801-1, Edition 1.0 2017-11)
The standard link impedance is 100 Ω. (The older 1995 version of the standard also permitted 120 Ω and 150 Ω in classes A-C, but this was removed from the 2002 edition.)
The standard defines several classes of optical fiber interconnect:
OM1: Multimode fiber type 62.5 µm core; minimum modal bandwidth of 200 MHz*km at 850 nm
OM2: Multimode fiber type 50 µm core; minimum modal bandwidth of 500 MHz*km at 850 nm
OM3: Multimode fiber type 50 µm core; minimum modal bandwidth of 2000 MHz*km at 850 nm
OM4: Multimode fiber type 50 µm core; minimum modal bandwidth of 4700 MHz*km at 850 nm
OM5: Multimode fiber type 50 µm core; minimum modal bandwidth of 4700 MHz*km at 850 nm and 2470 MHz*km at 953 nm
OS1: Singlemode fiber type 1db/km attenuation at 1310 and 1550 nm
OS1a: Singlemode fiber type 1db/km attenuation at 1310 and 1550 nm
OS2: Singlemode fiber type 0,4db/km attenuation at 1310, 1383 and 1550 nm
DS/EN 50174-1 og -2: 2009
DS/EN 50174-1: Kablingsinstallation: Specifikation af installation og kvalitetssikring. A1 2011.
DS/EN 50174-2: Kabelinstallation: Installationsplanlægning og praksis i bygninger. A1 2011
Udgave 2011, kapitel 8.3.8.3.1 beskriver pladskrav for rack i bygninger.
- 1,2 meter plads foran låger
- Rumhøjde min.2,6 m
- edb-gulv min. 200mm
- Lys min 500 lux, 1m over gulv
Udgave 2011, kapitel 4 og 5 beskriver kvalitetsplan.
I løbet af 2012 kommer tillæg vedr. PoE.
DS/EN 50310: 2010. Anvendelse af potentialudligning og jording i bygninger med informationsteknologiudstyr
Vægrack minimum 4 mm2.
Gulvrack minimum 16 mm2
Hvis afstand til potentialudlignings-bus maks. 10m, ellers forøges tværsnit.
EN 50600 Informationsteknologi - Datacenterfaciliteter og -infrastrukturer 2012-2014
Del 1: Generelle koncepter
Del 2-2: Strømfordeling
Del 2-3: Miljøkontrol
Del 2-1: Bygningskonstruktion
Del 2-4: Telekommunikationskablers infrastruktur (Forslag)
Del 2-6: Ledelse og operationel information (Forslag)